Best practices

Legionella control in hot and cold water systems: temperature, written schemes and testing

HSE temperature targets for hot and cold water, when a written control scheme is required, and why routine microbiological testing is not usually needed in enclosed systems that stay under control.

AMAADOR Academy editorial teamPublished 8 min read3 sources

Insulated tanks and pipework in a plant room, with gauges that are not treated as real readings.
Photograph created for AMAADOR Academy. It illustrates the practice described in this article and does not depict a real incident, audit or named workplace. Changes made: resized and re-compressed (JPEG and WebP versions).

Legionella bacteria can grow in purpose-built water systems. For hot and cold water systems, the Health and Safety Executive (HSE) gives clear temperature targets: cold water systems should be maintained, where possible, at a temperature below 20°C; hot water should be stored at least at 60°C and distributed so that it reaches a temperature of 50°C (55°C in healthcare premises) within 1 minute at the outlets.1

You must take a risk assessment and review it if there are significant changes — HSE’s examples include expansion of the water system and changes in resident population. You also need to consider the susceptibility of staff, including those more at risk of infection because of age or illness.1

Prevention comes first. HSE states that you should first consider whether you can prevent the risk of legionella by looking at the type of water system you need — for example, whether it is possible to replace a wet cooling tower with a dry air-cooled system. If you are unable to prevent the risk, you must introduce a course of action called a written control scheme.2

Criteria that should lead the work

  • Can the risk be prevented by the design or type of system, rather than only managed after installation?
  • Are cold water temperatures kept, where possible, below 20°C, and is hot water stored at least at 60°C and reaching 50°C (55°C in healthcare premises) within one minute at outlets?
  • Is there a current risk assessment, reviewed if the system or the people who may be exposed change significantly?
  • If the risk cannot be prevented, is there a written control scheme that describes the system, who is responsible, safe operation, the control methods, and the checks and their frequency?
  • Is microbiological testing used for the right kind of system, and not as a substitute for temperature control or for the written scheme?

Three common approaches

Temperature control without a living scheme

Keeping stored hot water hot enough, and cold water cold enough, is a core control for hot and cold water systems. It still fails if nobody owns the checks, if outlets are not actually reaching the target within a minute, or if a system expansion or a change in who lives or works in the building is never fed back into the assessment.1

Occasional sampling in place of control

Some sites commission a laboratory test and treat a clear result as proof that the system is under control. For generally enclosed hot and cold water systems, HSE states that significant contamination is less likely than in cooling towers and that microbiological monitoring is therefore not usually required. Testing for legionella may be necessary where there is doubt about the control regime’s effectiveness — for example where recommended temperatures or disinfection concentrations are not being consistently achieved.3 A sample cannot repair a system that is not meeting those temperatures.

A written control scheme, with testing where it belongs

The written control scheme is HSE’s required course of action when you cannot prevent the risk. It should describe the system, for example by developing a schematic diagram; who is responsible for carrying out the assessment and managing its implementation; the safe and correct operation of the system; what control methods and other precautions you will be using; and what checks will be carried out, and how often, to ensure the controls remain effective.2 For open systems such as cooling towers, evaporative condensers and spa pools, routine testing should be carried out at least quarterly, and there may be circumstances where more frequent sampling is required.3

How three approaches support legionella control. This compares categories of practice, not named water-treatment products or laboratory brands.
CriterionTemperature checks onlyOccasional sampling as the main controlWritten scheme, with testing where it belongs
HSE hot and cold temperature targetsCan support them, if outlets are actually checkedEasy to skip if a sample was clearBuilt into the described checks and their frequency
Ownership and review of the assessmentOften informalOften left with a contractor’s reportThe scheme names who is responsible and is reviewed after significant changes
Enclosed hot and cold systemsThe usual first line of controlRoutine microbiological monitoring is not usually requiredTesting when there is doubt about temperatures or disinfection, not as a ritual
Open systems (cooling towers, evaporative condensers, spa pools)Temperature alone is not the whole pictureA one-off sample is not a quarterly routineRoutine testing at least quarterly, and more often if needed
Main failure modeTargets exist on paper, but outlets and ownership are not checkedA laboratory result used to postpone basic temperature controlA scheme that is not updated when the system or the occupants change

What the scheme has to describe

HSE’s list is practical rather than decorative: a schematic of the system, named responsibilities, safe and correct operation, the control methods, and the checks with their frequency. The same pages also stress maintaining cleanliness of the water system. The mechanisms and frequency for cleaning depend on the system you have and on whether cleaning or disinfecting is routine or a response to a problem identified during monitoring.2

Hands checking a washbasin outlet as an illustration of temperature-control practice.
Photograph created for AMAADOR Academy. It illustrates the practice described in this article and does not depict a real incident, audit or named workplace. Changes made: resized and re-compressed (JPEG and WebP versions).

Checking an outlet is useful only if you know what “good” looks like: for hot water, HSE’s figure is 50°C (55°C in healthcare premises) within one minute; for cold water, below 20°C where possible. If those temperatures are not consistently achieved, that is exactly the kind of doubt HSE gives as a reason to consider testing for legionella in an otherwise enclosed system — not a reason to ignore the temperature fault.13

Video: “Health and safety risk assessment and management”, from Health and Safety Executive. Press play to load a privacy-enhanced YouTube player (youtube-nocookie.com).

The official HSE film “Health and safety risk assessment and management” is about the practice of assessing and managing risk, not a demonstration of a water-treatment product, a dosing pump or a sampling kit. Use it as context for the risk assessment and the written control scheme, not as a substitute for HSE’s legionella pages.

Occupational health and safety context is covered in ISO 45001 OH&S Awareness. For a walk-through of assessment practice, including job hazard analysis, see Risk Assessment & Job Hazard Analysis. These are independent awareness and exam-preparation courses. They are not official IRCA, ISO, NEBOSH or IOSH awards, and they are not a substitute for a licensed standard or for legal compliance.

A practical way to decide

Ask first whether the system itself can prevent the risk. If it cannot, write down how the system works, who owns it, how it should be operated, and which checks will show that the controls still work. Keep hot and cold temperatures in line with HSE’s figures, review the assessment after significant changes, use routine quarterly testing for open systems, and reserve microbiological testing of enclosed hot and cold systems for when the control regime is in doubt.123

Do not treat a single clear sample as a written control scheme, and do not leave a healthcare or other higher-risk setting on a 50°C distribution target if HSE specifies 55°C at outlets in healthcare premises.

Legionella control in hot and cold water systems: temperature, written schemes and testing

Frequently asked questions

What temperatures does HSE give for hot and cold water systems?

HSE states that cold water systems should be maintained, where possible, at a temperature below 20°C. Hot water should be stored at least at 60°C and distributed so that it reaches a temperature of 50°C (55°C in healthcare premises) within 1 minute at the outlets.

When is a written control scheme required?

HSE states that if you cannot prevent the risk of legionella, you must introduce a course of action called a written control scheme. It should describe the system (for example with a schematic diagram), who is responsible, the safe and correct operation of the system, the control methods, and what checks will be carried out and how often.

Do enclosed hot and cold water systems need routine legionella testing?

HSE states that for generally enclosed hot and cold water systems, microbiological monitoring is not usually required. Testing may be necessary where there is doubt about the control regime’s effectiveness — for example where recommended temperatures or disinfection concentrations are not being consistently achieved. Open systems such as cooling towers, evaporative condensers and spa pools should be routinely tested at least quarterly.

Sources

Every factual statement marked with a number links to the source below. Sources were retrieved on 22 November 2026; check the publisher for later revisions.

  1. Hot and cold water systems — HSE hse.gov.uk
  2. Legionnaires’ disease – what you must do — HSE hse.gov.uk
  3. Testing and monitoring your water system for legionella — HSE hse.gov.uk