Customize this training

Get a certificate — $16.67$5

Arc Flash Safety Awareness (NFPA 70E)

Arc Flash Safety Awareness (NFPA 70E)

Recognise arc flash hazards, read equipment labels and boundaries, choose arc-rated PPE and insist on an electrically safe work condition before anyone works on electrical equipment.

What you will learn

  • Explain what an arc flash and arc blast are, what causes them and how they injure people.
  • Identify the main rules and standards on arc flash (OSHA, NFPA 70E, IEEE 1584, UK EAWR, NF C 18-510) and who may do electrical work.
  • Apply the hierarchy of risk controls and justify energized work only in the rare cases allowed, using an energized work permit.
  • Read an arc flash label and use the shock approach boundaries and the arc flash boundary on the job.
  • Select, wear and care for arc-rated PPE using either the incident energy method or the PPE category method.
  • Establish an electrically safe work condition step by step and respond correctly to an arc flash incident.

Modules

  1. What an arc flash is and how it injures
  2. Rules, standards and who may do the work
  3. Controlling the risk: de-energize first
  4. Boundaries and arc flash labels
  5. Arc-rated PPE: selection, wearing and care
  6. Electrically safe work condition and emergency response

Course facts

Level
Awareness
Estimated study time
about 45 minutes
Final assessment
24 questions · Pass mark 80%
Available in
English
Price
Free. Optional verifiable certificate: $5
Last updated
Published by
AMAADOR ACADEMY

Who this course is for

Electricians, maintenance technicians, operators who switch or rack equipment, supervisors who issue permits, and HSE staff in plants, utilities, oil and gas, data centres and large buildings.

Prerequisites

Basic knowledge of electrical equipment (panels, switchgear, motor control centres) is helpful. No prior arc flash training required.

Course content

1. What an arc flash is and how it injures

An electric arc is current flowing through the air between two conductors, or between a conductor and earth, instead of through the wires meant to carry it. Once it starts, the air turns into a conducting plasma and the arc keeps itself going until a protective device clears the fault.

OSHA describes the result as a kind of electrical explosion: a brilliant flash of superheated gas, with temperatures OSHA puts above 35,000 °F (about 19,400 °C). The arc vaporises copper and aluminium. The metal expands violently, which creates the arc blast: a pressure wave, a very loud bang and flying molten metal.

An arc flash event hurts people in several ways at once.

Arc flash is different from electric shock. Shock needs your body to become part of the circuit. Arc flash does not: you can be badly burned without touching anything, simply by standing in front of an open panel when it fails.

HazardWhat hurts youMain protection
ShockCurrent through the bodyDe-energize, insulation, distance, rubber gloves
Arc flashRadiant and convective heatDe-energize, reduce energy, distance, arc-rated PPE
Arc blastPressure, noise, projectilesDe-energize, closed doors, remote operation, distance

2. Rules, standards and who may do the work

Arc flash rules come from laws (enforced by a regulator) and from consensus standards (which explain how to comply). Know which ones apply on your site.

DocumentTypeWhat it covers
OSHA 29 CFR 1910 Subpart S (1910.331-.335)US lawElectrical safe work practices: de-energize first, lockout/tagout, protective equipment, alerting techniques
OSHA 29 CFR 1910.269US lawPower generation, transmission and distribution, including arc-flash clothing rules
NFPA 70EUS consensus standard, used worldwideElectrical safety program, risk assessment, boundaries, labels, PPE, electrically safe work condition
IEEE 1584Engineering guideHow engineers calculate incident energy and the arc flash boundary
UK Electricity at Work Regulations 1989 and HSE HSG85GB law and guidanceDead working as the rule; live work only when strictly justified
NF C 18-510 and Code du travail (France)French standard and lawHabilitation électrique, operations on or near electrical installations

OSHA explains that NFPA 70E was originally developed at OSHA's request and assists in complying with OSHA 1910 Subpart S and 1926 Subpart K. NFPA 70E itself is a consensus standard, not a federal regulation. Many companies outside the United States also write NFPA 70E into their electrical safety rules and contractor requirements.

3. Controlling the risk: de-energize first

NFPA 70E requires the electrical safety program to use the hierarchy of risk controls. You start at the top and only move down when the higher control is not possible. PPE is the last line, not the first.

LevelArc flash example
1. EliminationEstablish an electrically safe work condition: no energy, no arc
2. SubstitutionReplace equipment with a design that reduces exposure, such as arc-resistant switchgear
3. Engineering controlsFaster protection (arc flash relays, maintenance mode switches, current-limiting fuses), remote racking and switching, finger-safe components, infrared windows
4. AwarenessArc flash labels, signs, barricades
5. Administrative controlsProcedures, permits, job briefings, training, qualified persons only
6. PPEArc-rated clothing, face and head protection, gloves, hearing protection

Engineering controls work by attacking the three factors that drive incident energy. Lower fault current usually means less energy, but only if the protective device still clears quickly: some devices trip more slowly at lower current, which can raise the energy, so any change must be checked by the arc flash study. Shorter clearing time means a shorter arc, and this is often the biggest lever. Greater distance means less energy reaches the worker, which is why remote racking devices and remote switching are so effective.

4. Boundaries and arc flash labels

NFPA 70E uses distances from exposed energized parts to decide who may come closer and what protection they need. There are two shock boundaries and one arc flash boundary. They are independent: whichever is larger at a given spot controls access.

BoundaryBased onRule
Limited approach boundaryShockUnqualified persons may cross only if escorted and informed by a qualified person
Restricted approach boundaryShockOnly qualified persons, with shock protection, for justified work
Arc flash boundaryBurnsAnyone inside must wear arc flash PPE for the hazard

Shock boundaries come from a table in NFPA 70E based on voltage. For example, for common 3-phase systems between 151 V and 750 V the table gives a limited approach boundary of 3.05 m (10 ft) for an exposed movable conductor, 1.07 m (3 ft 6 in) for an exposed fixed circuit part, and a restricted approach boundary of 0.3 m (1 ft). Always use the values on your label or in your site procedure.

The arc flash boundary is the distance at which incident energy falls to 1.2 cal/cm² (5 J/cm²), the onset of a second-degree burn on bare skin. It is not set by voltage. It comes from the arc flash risk assessment and depends on fault current and clearing time. On some equipment it is under a metre; on large switchgear with slow protection it can be many metres, well beyond the room door.

5. Arc-rated PPE: selection, wearing and care

NFPA 70E lets the employer choose PPE by one of two methods for a given piece of equipment. They must not be mixed on the same equipment.

1. Incident energy analysis method

An engineer calculates the incident energy at the working distance, usually with IEEE 1584. You then select arc-rated clothing and equipment with an arc rating equal to or greater than the calculated incident energy. The label shows the value.

2. Arc flash PPE category method

NFPA 70E tables give a PPE category for common tasks and equipment, provided the equipment stays within stated limits of available fault current and fault clearing time and the stated working distance. If the equipment is outside those limits, or the limits are unknown, the table cannot be used and an incident energy analysis is needed.

PPE categoryMinimum arc ratingTypical clothing
14 cal/cm²Arc-rated shirt and trousers or coverall, arc-rated face shield or hood
28 cal/cm²Arc-rated shirt and trousers or coverall, arc-rated face shield and balaclava, or hood
325 cal/cm²Arc flash suit (jacket, trousers or coverall) and hood, arc-rated gloves or rubber insulating gloves with leather protectors
440 cal/cm²Arc flash suit and hood rated at least 40 cal/cm², arc-rated gloves or rubber insulating gloves with leather protectors

6. Electrically safe work condition and emergency response

An electrically safe work condition (ESWC) is the state in which a conductor or circuit part has been disconnected, locked out, tested to confirm the absence of voltage and, where needed, temporarily grounded. Until all of that is done, NFPA 70E treats the equipment as energized, and so does OSHA 1910.333.

  1. Identify all sources — use up-to-date drawings, diagrams and labels. Look for back-feeds, generators, UPS, capacitors and PV.
  2. Interrupt the load, then open the disconnect — for each source.
  3. Visually verify — where possible, see that switch blades are fully open or drawout breakers are withdrawn to the fully disconnected position.
  4. Release stored energy — discharge capacitors, block or release mechanical energy.
  5. Apply lockout/tagout — each worker applies a personal lock according to the written procedure.
  6. Test for absence of voltage — with an adequately rated instrument, test each phase conductor or circuit part phase to phase and phase to ground. Check the tester on a known source before and after the test.
  7. Ground if needed — where induced voltage or stored energy could re-energize the parts, apply temporary protective grounds rated for the available fault current.

The full lesson continues in the interactive course on this page.

Sources and references

Awareness training only. It does not make you a qualified person under NFPA 70E or OSHA, an authorised person under the UK Electricity at Work Regulations, or habilité under NF C 18-510. Those require employer-provided practical training, assessment and written authorisation. Always follow your site's electrical safety program and the current edition of the standards that apply where you work. NFPA 70E is a copyrighted consensus standard: read the official text for exact requirements.

All courses · Occupational Safety — Free courses, certificate $5 | AMAADOR ACADEMY