CEA — Certified Energy Auditor (Exam-Prep)
Independent exam-prep over the public AEE Certified Energy Auditor body of knowledge, with original practice questions and a final exam.
CEA Exam Prep: Certified Energy Auditor Course (Free) is a free, self-paced online course from AMAADOR Academy. Independent exam-prep over the public AEE Certified Energy Auditor body of knowledge, with original practice questions and a final exam. It is independent exam-prep built from the syllabus published on this page. An optional verifiable certificate costs $29.
Last updated: June 2026
An independent, free exam-preparation course built over the publicly published AEE Certified Energy Auditor body of knowledge. It walks the full syllabus — the audit process and ASHRAE levels, utility-bill analysis and energy accounting, the building envelope, HVAC, lighting, motors and drives, compressed air, measurement and verification (IPMVP), engineering economics, energy management (ISO 50001) and safety — with visual lessons, worked numbers, original self-check questions and a 10-question final exam. It is awareness/preparation only and is NOT the official AEE course or exam, and is not affiliated with or endorsed by AEE. It maps to AEE Certified Energy Auditor body of knowledge. The course is organized into 9 modules, ending with a final exam (pass mark 70%). It is independent, free exam-preparation training — not an official or accredited review course.
What you'll learn
- Module 1 — The Energy-Audit Process & ASHRAE Levels
- Module 2 — Utility Bill Analysis & Energy Accounting
- Module 3 — Building Envelope & Heat-Transfer Fundamentals
- Module 4 — HVAC Systems & Efficiency
- Module 5 — Lighting, Motors, Drives & Compressed Air
- Module 6 — Measurement & Verification (IPMVP)
- Module 7 — Engineering Economics, Reporting & Payback
- Module 8 — Energy Management (ISO 50001) & Continuous Improvement
- Module 9 — Audit Safety, Instruments & Professional Ethics
Learning objectives
- Understand that this is independent CEA exam-prep over the public AEE body of knowledge — not the official AEE course, exam or endorsement
- Run the energy-audit process and distinguish the ASHRAE audit levels (Preliminary, Level I, II and III)
- Analyse utility bills, build an energy account, and compute Energy Use Intensity (EUI) and demand for benchmarking
- Reason about the building envelope (U-value, R-value, infiltration) and HVAC as the largest energy end-uses
- Find and quantify savings in lighting, electric motors, variable-speed drives and compressed-air systems
- Apply measurement & verification using the four IPMVP options and an adjusted baseline
- Use engineering economics — simple payback, life-cycle cost, NPV and IRR — to rank measures honestly
- Connect findings to an energy management system (ISO 50001 Plan-Do-Check-Act) and audit safety
- Sit a 10-question, exam-style final exam (70% to pass) built from original questions
Frequently asked questions
What is the CEA Exam Prep: Certified Energy Auditor Course (Free) course?
CEA Exam Prep: Certified Energy Auditor Course (Free) is a free, self-paced online course from AMAADOR Academy. Independent exam-prep over the public AEE Certified Energy Auditor body of knowledge, with original practice questions and a final exam.
Who is the CEA Exam Prep: Certified Energy Auditor Course (Free) course for?
It is independent exam-prep for learners working through the syllabus published on this page.
Is this course free, and how is it delivered?
Yes. The course is free, self-paced and online. You can work through the lessons at your own pace. An optional verifiable certificate costs $29.
Is this the official CEA Exam Prep: Certified Energy Auditor Course (Free) course or exam?
It is awareness/preparation only and is NOT the official AEE course or exam, and is not affiliated with or endorsed by AEE.
How do I get a certificate?
After you complete the course and pass the final exam (pass mark 70%), you can order an optional verifiable certificate of completion for $29.
Course facts
- Estimated study time
- about 3 hours
- Final assessment
- 130 questions · Pass mark 70%
- Available in
- English, Français
- Price
- Free. Optional verifiable certificate: $15
- Last updated
- Published by
- AMAADOR ACADEMY
Course content
1. Energy Auditing Fundamentals & Audit Levels (ASHRAE)
An energy audit is a systematic study that quantifies how a facility uses energy, identifies Energy Conservation Measures (ECMs), and ranks them by cost-effectiveness. For the AEE Certified Energy Auditor (CEA) exam you must master the vocabulary, the standardized audit levels, and the core calculations that turn raw utility data into a defensible recommendation. This chapter is foundation-level material that recurs throughout the body of knowledge.
Core definitions you must not confuse
Key terms.Energy audit = analysis of consumption and savings opportunities. Energy assessment / survey = looser synonyms; the survey is the on-site data-gathering activity. Commissioning (Cx) verifies systems perform to design intent; retro-commissioning (RCx) applies that to existing buildings that were never commissioned. Measurement & Verification (M&V) confirms realized savings after implementation (IPMVP).
The ASHRAE audit levels
The governing framework is ASHRAE Standard 211 (Standard for Commercial Building Energy Audits), which superseded the older three-level descriptions in the ASHRAE Procedures publication. It defines a Preliminary energy use analysis plus Levels 1, 2 and 3. Expect direct questions on what each level includes and excludes.
2. Audit Instrumentation & Data Collection
An energy audit is only as credible as the data behind it. The CEA body of knowledge expects you to know which instrument measures which quantity, how accurate it is, how to deploy it safely, and how to convert raw readings into defensible energy and cost figures. This chapter covers the metering toolkit, measurement theory, and the data-collection workflow that separates a Level 1 walk-through from a defensible Level 2/3 audit (per ASHRAE Standard 211).
The core instrument toolkit
Each measured parameter maps to a specific instrument class. Memorize the pairings — exam questions frequently ask "which tool measures X?"
| Instrument | Measures | Key spec / unit | Watch out for |
|---|---|---|---|
| True-RMS power logger | kW, kWh, V, A, power factor, harmonics | kW; PF 0–1 | Use true-RMS for non-linear (VFD) loads; averaging meters under-read |
| Clamp-on (CT) ammeter | Current on a live conductor | Amps | Clamp ONE conductor only; CT polarity/orientation |
| Infrared camera | Surface temperature, thermal anomalies | °C/°F; emissivity | Set emissivity (~0.95 for most building surfaces); reflective metals mislead |
| Flue-gas analyzer | O₂, CO, CO₂, stack temp → combustion efficiency | % O₂, ppm CO | High excess air = wasted heat; CO spike = unsafe |
| Ultrasonic / vane flow meter | Liquid or air velocity & flow | m/s, CFM, GPM | Need straight pipe run upstream for accuracy |
3. Building Envelope & Thermal Analysis
The building envelope — the physical separator between conditioned interior and the outdoors — governs a large share of a building's heating and cooling load. For the CEA exam you must master the three coupled heat-transfer mechanisms, the U-factor / R-value relationship, infiltration, and the standards (ASHRAE 90.1, the IECC) that set baseline performance. Envelope questions are heavily numerical, so memorize the formulas and unit conventions below.
Heat Transfer Fundamentals
Heat crosses the envelope by conduction (through solid assemblies), convection (air films and cavities), and radiation (sky, sun, surfaces). Envelope calculations bundle these into a single steady-state coefficient.
Core relationships: R = thickness / k (per inch: R = 1/k). Assemblies in series add: Rtotal = ΣRi. U = 1 / Rtotal. Conductive load: Q = U × A × ΔT (Btu/h), where A is area (ft²) and ΔT the temperature difference (°F).
Worked U-factor Example
A wall: outside air film R-0.17, brick R-0.44, R-13 cavity batt, gypsum R-0.45, inside air film R-0.68.
| Layer | R-value |
|---|---|
| Outside air film | 0.17 |
| Brick veneer | 0.44 |
| Cavity insulation | 13.00 |
| Gypsum board | 0.45 |
| Inside air film | 0.68 |
| Rtotal | 14.74 |
4. HVAC System Audits & Efficiency
Heating, ventilation and air-conditioning (HVAC) typically drives 40–60% of commercial building energy and is where a Certified Energy Auditor finds the largest, most defensible savings. The exam tests whether you can read a system, quantify how it is operated, and propose costed measures that survive an interactive-effects check. Start by classifying the system, then interrogate how it is controlled — most waste is operational, not mechanical.
Classifying the system
Air-side systems split into constant-volume (CV) and variable-air-volume (VAV). Old terminal-reheat and dual-duct CV systems simultaneously cool then reheat air — a classic energy crime. Water-side plant runs chillers (air- or water-cooled), boilers and the distribution pumps that serve them. Packaged rooftop units (RTUs) dominate small commercial; built-up central plant dominates large buildings.
Efficiency metrics — know the units cold
The exam loves metric confusion. Chiller efficiency is kW/ton (lower is better; ~0.5–0.6 for an efficient water-cooled centrifugal, ~1.0+ at part load for older units). COP is dimensionless output/input. EER (Btu/h per watt) and seasonal SEER2/IEER rate unitary equipment. Boiler performance is combustion vs seasonal (AFUE) efficiency. One ton of refrigeration = 12,000 Btu/h; COP = EER ÷ 3.412.
5. Lighting Audits & Retrofits
Lighting is the highest-yield system in most commercial energy audits: it typically represents 20–40% of a commercial building's electricity and offers the fastest, most predictable paybacks. The CEA exam expects you to quantify existing systems, calculate retrofit savings (including HVAC interaction), and verify the result. This chapter covers the measurement, math, and traps.
Photometric fundamentals you must know cold
- Luminous flux — total light output, measured in lumens (lm).
- Illuminance — light arriving on a surface, in footcandles (fc) = lumens/ft², or lux in SI (1 fc ≈ 10.76 lux).
- Luminance — brightness of a surface as seen by the eye (cd/m²); drives glare.
- Efficacy — lumens per watt (lm/W); the core efficiency metric for any source.
- CRI — Color Rendering Index (0–100); CCT — Correlated Color Temperature in kelvin (warm ~2700K, neutral ~3500K, cool ~5000K).
Lumen method (average illuminance):
E (fc) = (N × Llamp × LLF × CU) / Area (ft²)
where N = number of lamps, L = initial lumens/lamp, LLF = Light Loss Factor (LLD × LDD × ballast factor), CU = Coefficient of Utilization. Solve for N when designing to a target fc.
6. Electrical, Motors & Compressed-Air Audits
Electrical loads, motor systems, and compressed air are where most industrial energy dollars hide. The CEA candidate must read a bill, measure real loads safely, and quantify savings from power factor correction, motor right-sizing, and leak repair. This chapter covers the core measurements, formulas, and exam traps.
Reading the Electric Bill
Industrial tariffs bill three components: energy (kWh), demand (kW, usually the highest 15- or 30-minute average in the month), and often a power factor (PF) penalty. A common exam trap: demand and energy are different charges — shaving peak kW lowers demand cost even if total kWh is unchanged. Load factor = average load / peak load = kWh / (peak kW × hours). A low load factor (spiky profile) signals demand-management opportunity.
Key power formulas
- Three-phase real power: P (kW) = √3 × V × I × PF / 1000
- Power factor: PF = kW / kVA = cos φ
- Capacitor kVAR needed = kW × (tan φ₁ − tan φ₂)
Power Factor Correction
PF is the ratio of real power (kW) to apparent power (kVA). Inductive loads — motors, transformers, fluorescent ballasts — draw reactive power (kVAR) that does no work but loads conductors and triggers utility penalties. Correction adds capacitors to supply reactive power locally, raising PF toward unity (target 0.95–0.98, not 1.0 to avoid leading-PF resonance).
7. Auditing Thermal, Boiler & Steam Systems
Combustion and steam systems are usually the single largest fuel consumer on a CEA audit site. Because losses compound — combustion, distribution, then end use — small percentage gains on a large gas bill yield big savings. The CEA Body of Knowledge expects you to quantify combustion efficiency from a flue-gas analysis, value steam losses (traps, leaks, insulation), and recommend recovery measures (economizers, blowdown heat recovery, condensate return). This chapter gives you the numbers and the method.
1. Combustion efficiency — the heart of the boiler audit
Boiler combustion efficiency = 100% − stack losses − radiation/convection losses. The dominant, measurable loss is dry flue-gas loss, driven by stack temperature and excess air. You read it with a flue-gas analyzer measuring O₂ (or CO₂), CO, and net stack temperature (flue temp − combustion-air temp).
Excess air from O₂: EA(%) ≈ O₂ / (20.9 − O₂) × 100. At 3% O₂ → ≈ 16% excess air. Rule of thumb: every 1% reduction in excess O₂ (toward the safe minimum) ≈ 0.5–1% fuel saving; every 22 °C (40 °F) drop in net stack temperature ≈ 1% efficiency gain.
8. Module 8 — Measurement & Verification (IPMVP) and Savings Calculations
An energy audit recommends measures; Measurement & Verification (M&V) proves they worked. Because you cannot simultaneously meter a building as it actually ran and as it would have run without the project, savings are never measured directly — they are calculated as a difference. The governing principle of the International Performance Measurement & Verification Protocol (IPMVP), published by the Efficiency Valuation Organization (EVO), is the foundation tested on the CEA exam.
The fundamental savings equation
Savings = (Baseline-period energy − Reporting-period energy) ± Adjustments
Adjustments bring both periods to a common set of conditions. "Avoided energy use" adjusts the baseline to reporting-period conditions; "normalized savings" adjusts both to a fixed normal year.
Why adjustments are everything
The naive "compare last year's bill to this year's bill" is wrong because weather, occupancy, production and operating hours change. M&V isolates the project's effect by mathematically correcting for those independent variables. A measure that saved 12% can look like 2% in a hot summer unless you weather-normalize.
Two kinds of adjustment
9. Economic Analysis of Energy Conservation Measures
For the CEA exam, economic analysis is where a technically sound retrofit becomes a fundable project. Examiners test whether you can compute, compare, and correctly interpret the financial metrics that justify an energy conservation measure (ECM). Expect numeric problems with given cash flows, energy savings, and a discount rate — know the formulas cold and watch the unit and sign conventions.
Core metrics you must master
Simple Payback Period (SPP)
SPP = Initial Cost ÷ Annual Savings. It ignores the time value of money, escalation, salvage, and measure life — so it overstates attractiveness of short-lived measures and is only a screening tool.
Time value of money
Present worth of a future amount: PV = FV ÷ (1+i)n. Present worth of a uniform annual series uses the Uniform Present Worth (USPW) factor: USPW = [1 − (1+i)−n] ÷ i. Multiply annual savings by USPW to get the present value of the savings stream.
Net Present Value, IRR, and SIR
NPV = (present value of all savings and salvage) − initial investment. Accept if NPV > 0. When comparing mutually exclusive ECMs, the highest NPV wins. IRR is the discount rate that drives NPV to zero; accept when IRR exceeds the organization's MARR (minimum acceptable rate of return / hurdle rate). SIR = present value of savings ÷ present value of costs; accept if SIR > 1.0. SIR is the federal (FEMP / 10 CFR 436) preferred ranking metric and is essentially a benefit–cost ratio.
10. Audit Reporting & Implementation
The audit report is the deliverable that converts field data into capital decisions. On the CEA exam, expect questions on report structure, ASHRAE audit levels, the economic metrics that rank measures, M&V protocols, and how to present recommendations so management acts on them. A technically perfect audit that produces an unreadable or non-actionable report is a professional failure.
The CEA Report: Required Anatomy
AEE and ASHRAE expect a consistent skeleton. The exam tests whether you know what belongs where and which sections decision-makers actually read.
ASHRAE Audit Levels (know these cold):
- Preliminary / Level 0 — Benchmarking: EUI comparison, walk-through, no detailed measures.
- Level 1 — Walk-Through: low-cost/no-cost measures, rough savings, identifies capital projects worth deeper study.
- Level 2 — Energy Survey & Analysis: the workhorse — detailed savings/cost for each ECM, breakdown of energy by end use, practical financial analysis.
- Level 3 — Detailed / Investment-Grade: rigorous engineering, capital-intensive measures, hourly simulation, suitable for financing decisions.
Ranking Measures: The Economics That Drive the Report
Recommendations must be prioritized by economics, not just energy saved. The exam expects fluency with each metric and its limits.
The full lesson continues in the interactive course on this page.